Two compact fire-and-smoke detectors missed different shares of D-Fire images at the same cutoff. Calibration brought average misses near chosen targets, but smoke-only scenes and changing conditions remain challenges.

AI-generated conceptual illustration for Calibrating thresholds for fire detector alarms
AI-generated conceptual illustration; not documentary evidence.

A detector can identify fire or smoke in an image yet still lead to a missed alarm. This study tests ways to turn detection boxes into image-level decisions and choose thresholds to limit misses—using one benchmark, two existing models and a method whose guarantees depend on future images resembling the calibration data.

A camera-based fire system must make a simple decision: should this image trigger an alarm? Object detectors provide candidate boxes and confidence scores, but the same confidence cutoff can behave differently across models. And measuring how well a detector draws boxes does not directly tell us how often an alarm system misses an image containing fire or smoke.

Vikas Sandireddy’s study focuses on that gap. It asks whether a threshold selected from held-out examples can control image-level misses better than a fixed cutoff, and whether the rule for combining detections into one image score affects the results.

Turning boxes into an alarm

The paper evaluates two publicly available compact detectors, YOLOv8n and YOLOv5s, on the 4,306-image D-Fire test set. The author did not train either detector. Instead, predicted boxes were converted into one score per image using three rules: take the highest-confidence box; combine up to the three strongest boxes with a “noisy-OR” rule, allowing several weaker detections to add up; or take the strongest box while ignoring boxes covering less than 0.1% of the image.

An image counted as positive if it had at least one fire or smoke annotation, and negative if it had neither. The study used a split conformal procedure to select a threshold from positive calibration images. In plain terms, the threshold is chosen using the scores on those images so that, if calibration and future positive images are exchangeable—roughly, drawn in comparable ways—the expected fraction of missed positive images is bounded by a chosen target. The tested targets were 10%, 5% and 1%.

Because there was only one test split, the author repeatedly divided its images into calibration and evaluation halves, preserving the proportions of the dataset’s categories, and averaged results across 200 random splits. This tests the threshold method on D-Fire; it is not a test of a deployed monitoring system under changing real-world conditions.

One cutoff, different miss rates

With the maximum-box-score rule and a fixed confidence threshold of 0.5, YOLOv8n missed 17.3% of positive images, while YOLOv5s missed 8.4%. The result shows that the same cutoff did not produce the same miss rate for these two detectors on this dataset.

Across both models, all three scoring rules and all three targets, average miss rates on evaluation halves were at or just below the selected targets. At the 5% target, false alarm rates on negative images ranged from 1.2% to 3.0%. At the stricter 1% miss target, false alarm rates rose to between 6.7% and 21.9%, depending on the detector and scoring rule. In this benchmark, pursuing fewer missed positives therefore came with more false alarms, particularly at the strictest target.

The overall average also concealed a weakness in one category. At the 5% target, smoke-only images were detected only 91.8% of the time by YOLOv8n and 91.4% by YOLOv5s with the maximum-score rule—below the 95% detection rate corresponding to a 5% miss rate. Images containing both fire and smoke were detected more often. The target applies to positive images as a group, not separately to every category.

The paper describes false alarms on scenes that resemble fire or smoke, including fog, clouds, lamps and other lights. Misses included very small or faint targets and potentially ambiguous labels, such as a white plume from a power plant marked as smoke. In the illustrated misses, the detectors produced no box even at the very low confidence level used to retain predictions. A threshold change cannot recover an image the detector did not detect at all.

What the results do—and do not—show

The statistical guarantee depends on calibration images being representative of future images. Changes in cameras, locations or weather could undermine that assumption. Results come from one dataset and two detectors, and the experiments use still images rather than video, where information across frames might matter. The guarantee also concerns the average across positive images; it does not ensure the same miss rate for smoke-only scenes or another subgroup.

The study makes a focused point: evaluate thresholds at the level of the decision a system actually makes, and do not assume a cutoff used for one model will deliver the same miss rate with another. It does not establish performance in real deployments or show that threshold calibration alone makes fire detection reliable.

The source is an arXiv preprint. The supplied material does not establish whether it has undergone peer review, so these results should be read as a benchmark study, not validated safety evidence.